1-CHKH-R
Power cable - fire retardant, halogen-free, for common installation
Construction:
1. Conductor Cu conductor of the category 1 or 2 according to IEC 60228
2. Insulation fire retardant halogen-free polymer compound
3. Cable core wrapping by PET foil
4. Bedding none
5. Screening none
6. Sheath fire retardant halogen-free polymer compound
Technical parameters:
Rated voltage U0/U: 0,6/1 kV AC
Highest voltage of the Um system:
Testing voltage between cores: 4 kV AC 5 min
Testing voltage between core and screening:
Surrounding temperatures (fixed placement): - 40°C up to + 90°C
Surrounding temperatures (during installation): -5°C up to +50°C
Minimum bending radius (fixed placement): 12D
Basic characteristics:
Self-extinguishing: EN 60332-1-2
Resistant to vertical spread of flame: EN 50266-2-2 category A
Halogen-free, low corrosion of gasses during burning: IEC 60754-2
Low smoke density during burning: IEC 61034-2
Colour marking of cores: HD 308 S2
Sheath colour: orange
Usage:
Fire retardant, halogen-free power cables are used for common installation in power circuits for the voltage up to 0,6/ kV. Due to its characteristics during fire they are used in the premises where is insisted on personal protection, on the protection of equipments, constructions and of materials (e.g. in public spaces, shopping malls, in hospitals, hotels or in tunnel constructions). It is possible to use them in dry or wet environment.
1-CXKH-R
Power cable – fire retardant, halogen-free, for common installation
Construction:
1. Conductor Cu conductor of the category 1 or 2 according to IEC 60228
2. Insulation XLPE
3. Cable core wrapping by PET foil
4. Bedding none
5. Screening none
6. Sheath fire retardant halogen-free polymer compound
Technical parameters:
The rated voltage: 0,6/1 kV AC
The highest voltage of Um system:
Testing voltage between cores: 4 kV AC 5 minute
Testing voltage between core and screening: 250 V AC 1 minute
Insulation resistance: > 1000 MΩ.km
Surrounding temperatures (fixed placement): -40°C up to +90°C
Surrounding temperatures (during installation): -5°C up to +50°C
Miminum bending radius (fixed placement): 12D
Basic characteristics:
Self-extinguishing: EN 60332-1-2
Resistant to vertical spread of flame: EN 50266-2-2 category A
Halogen-free, low corrosion of gasses during
burning: IEC 60754-2
Low smoke density during burning: IEC 61034-2
Colour marking of cores: HD 308 S2
Sheath color: orange
Usage:
Fire retardant, halogen-free power cables are used for common installation in power circuits for the voltage up to 0,6/ kV. Due to its characteristics during fire they are used in the premises where is insisted on personal protection, on the protection of equipments, constructions and of materials (e.g. in public spaces, shopping malls, in hospitals, hotels or in tunnel constructions). It is possible to use them in dry or wet environment.
The product is conformable with the direction EU 73/023/EEC for low voltage.